Skip to main content

Toccare Repeater Firmware Upgrade

How To: Upgrade your Toccare repeater panel firmware

Updated over a week ago

The tool used to update firmware is Flash Magic (version 7.40.3104 or later).

Firmware Upgrade General Information

To update the firmware, you need to load 2 different Hex files:

  • FLASH_ONEKBD.hex

  • SPIFI_ONEKBD.hex

  • SPIFI_LOGO.hex (optional)

The repeater panel must be powered.


How To: Upload the FLASH_ONEKBD.hex File

Panel Side:

  • Insert the Serial cable into Y3 connector

  • Insert the Serial cable (PC site connection) on the PC

  • Switch the SW1 to the left

  • Press the SW9 reset button
    At this point, the display turns off.

Personal Computer Side:

Run Flash Magic.exe

  • Select in the “Select” field LPC4088 in the ARM Cortex menu

  • Select into the “COM Port” field the used serial port number

  • Select into the “Baud Rate” field 115200 or 57600 value

  • Select into the “Interface” field None (ISP)

  • Select into “Hex File” the FLASH_ONEKBD.hex that is necessary to program into the board

  • Select into “Oscillator (MHz)” field 12 value

  • Check “Erase all Flash+Code Rd Prot”

  • Check “Verify after programming”

  • Press the “Start” button.

Turn off the Repeater and turn it back on. Do not change the position of SW1.

How To Upload the SPIFI_ONEKBD.hex File

Run Flash Magic.exe

  • Select in the “Select” field Generic SPI LPC4088 EA in the External Flash menu

  • Select into the “COM Port” field the used serial port number

  • Select into the “Interface” field None(ISP)

  • Select into “Hex File” the SPIFI_ONEKBD.hex that is necessary to program into the board

  • Check “Erase blocks used by Hex File”

  • Press the “Start” button on the Flash Magic tool.

    Turn off the Repeater and turn it back on. Do not change the position of SW1.

Optional: How To Upload the SPIFI.LOGO.hex File

By default, the panel will have the Eurotech Logo: if you need to change logo with a custom logo please follow the following procedure:

Run Flash Magic.exe

  • Select in the “Select” field Generic SPI LPC4088 EA in the External Flash menu

  • Select into the “COM Port” field the used serial port number

  • Select into the “Interface” field None(ISP)

  • Select into “Hex File” the SPIFI_LOGO.hex that is necessary to program into the board

  • Check “Erase blocks used by Hex File”

  • Press the “Start” button on the Flash Magic tool.

When all 3 files have been updated:

  • Remove the Serial cable from the board

  • Switch the button SW1 to the right

  • Press the SW9 button

Toccare Repeater's Serial Cable (for previous cards to TD587B version)

It’s a serial cable with one 9 pin female connector and one one-way connector connected as shown in figure.

Toccare Repeater's Serial Cable (for cards from TD587B version higher)

It’s a serial cable with one 9-pin female connector and one one-way connector connected as shown in the figure. The ONE2 slave FW update cable can be used.

Contact Information
For further assistance or if you have any questions regarding this procedure, please contact the Eurotech Technical Team:
Email: [email protected]
Phone: +44 (0) 203 141 0982

Important Notice:
This content is provided for informational purposes only and is intended solely for qualified personnel with appropriate training and expertise. Eurotech Fire Systems Ltd assumes no responsibility for the outcomes resulting from the use of this information. It is the user's responsibility to ensure all work is carried out in accordance with applicable regulations and standards.

Did this answer your question?