False Alarm Management – Advanced Panels

False Alarm Management with Advanced Panels.

Updated this week

Step 1:

Select the 'False Alarm Management' icon under 'Alarm Verification' the method is not selected.

Step 2:

Select type 'B' method -- the verification time will be defaulted to 240 second and all the smoke detectors are added by default.

If Heats and Multi's need to be added, change the '-' to 'ALL' using the drop-down menu. Under 'Verification Outputs', change the 'ALL' to '-' on the sounders and beacons.

All devices will now have a verification time of 240 seconds -- I.E., the fire condition will need to be persistent for this duration.

Contact Information
For further assistance or if you have any questions regarding this procedure, please contact the Eurotech Technical Team:
Email: [email protected]
Phone: +44 (0) 203 141 0982

Important Notice:
This content is provided for informational purposes only and is intended solely for qualified personnel with appropriate training and expertise. Eurotech Fire Systems Ltd assumes no responsibility for the outcomes resulting from the use of this information. It is the user's responsibility to ensure all work is carried out in accordance with applicable regulations and standards.