Skip to main content

Minimum Acceptable Test Values

Guide to minimum acceptable test values for BS 5839-1 fire alarm installations. Covers continuity, insulation resistance, earth fault testing, voltage drop calculations, visual inspection criteria, cable types, and includes a practical reuse checklist.

Updated this week

(Typical for BS 5839-1 Installations)

Note: BS 5839-1 does not always specify numerical values directly; it requires that wiring meets the electrical safety requirements of BS 7671 (IET Wiring Regulations). The values below reflect the standards normally applied in fire-alarm installation practice in the UK.


1. Continuity (CPC and Conductors)

Requirement: All conductors must show continuous, unbroken paths on the meter.

Acceptable value:

  • Resistance should be finite and stable (typically < a few ohms depending on cable length)

  • No open circuits

  • Correct polarity throughout


2. Insulation Resistance

Typical test voltage: 500 V DC
(Or 250 V DC if sensitive equipment is still connected.)

Minimum acceptable reading: ≥ 1 MΩ between:

  • Core to core

  • Core to screen (if present)

  • Core to earth

In many installations, engineers aim for > 2 MΩ to indicate healthy cable.


3. Earth Fault / Polarity

Must show:

  • Correct polarity on all circuits

  • No earth faults on any conductor

Earth fault current should be negligible (high resistance to earth).
Instruments typically show > 1 MΩ to earth.


4. Loop Resistance / Voltage Drop

Requirement: Voltage at devices must remain within manufacturer limits, typically:

  • Sounder circuits: not more than 10% voltage drop

  • Detector circuits: not below manufacturer minimum (often ~16–20 V depending on panel)

Acceptable cable resistance: Depends on the cable length and conductor size.

As a rule of thumb:

  • ~0.8 Ω per 100 m for 1.5 mm² fire-resistant cable

  • ~0.5 Ω per 100 m for 2.5 mm² cable

The test ensures the panel can supply enough current to the furthest device.


5. Visual Inspection Criteria

You must confirm:

Cable condition
✅ No crushing, cuts, rodent damage, scorch marks, damp ingress
✅ No joints unless using certified fire-rated connectors
✅ No unsupported spans or sagging

Routing
✅ Separated from high-voltage cables
✅ Protected where exposed
✅ Compliant with fire-stopping requirements
✅ No PVC cable used for critical paths

Fixings
✅ Metallic or fire-resistant fixings only
✅ Spacing compliant (typically every 300 mm–400 mm horizontally)


6. Cable Type Requirements (BS 5839-1 Summary)

BS 5839-1 defines two fire-resistant cable performance levels:

Standard Fire-Resistant Cable

Acceptable for:

  • Conventional systems in low-risk areas

  • Smaller buildings

  • Short escape routes

Examples:

  • Prysmian FP200 Gold

  • AEI Firetec Standard

Enhanced Fire-Resistant Cable

Required for:

  • Buildings where cables must sustain fire for extended durations

  • Critical areas (e.g., control rooms, multi-storey escape routes)

  • Systems needing operation during partial structural collapse

Examples:

  • Prysmian FP Plus

  • AEI Firetec Enhanced

⚠️ If existing cable is neither standard nor enhanced fire-resistant cable → it cannot be reused.


Simple On-Site Checklist

Existing Cable Reuse Checklist — BS 5839-1

Electrical Tests

☐ Continuity tested and satisfactory
☐ Polarity correct
☐ Insulation resistance ≥ 1 MΩ
☐ Earth faults clear
☐ Resistance/voltage drop acceptable for panel/device requirements

Visual Inspection

☐ Cable type confirmed as fire-resistant (standard/enhanced)
☐ No damage or deterioration
☐ Suitable fixings (metallic/fire-resistant)
☐ Correct segregation from LV/ELV
☐ Correct routing and protection
☐ Fire-stopping intact

Result

☐ Cable approved for reuse
☐ OR: Cable rejected (state reason)

Contact Information
For further assistance or if you have any questions regarding this procedure, please contact the Eurotech Technical Team:
Email: [email protected]
Phone: +44 (0) 203 141 0982

Important Notice:
This content is provided for informational purposes only and is intended solely for qualified personnel with appropriate training and expertise. Eurotech Fire Systems Ltd assumes no responsibility for the outcomes resulting from the use of this information. It is the user's responsibility to ensure all work is carried out in accordance with applicable regulations and standards.

Did this answer your question?